Model MDU-HP (High Power Design)
Providing Critical Power Distribution to the Datacenter The GE Series MDU-HP Monitored Distribution Unit provides a flexible design to provide three phase power to other distribution units and/or overhead busway. Each unit can be configured to provide isolation, voltage transformation, & voltage regulation. Up to (14) Subfeed CBs can be incorporated within the MDU-HP. Each unit internally uses GE Panelboards and Circuit Breakers. The MDU-HP can also provide subfeed CB monitoring to assist end users in determining branch circuit and total load to prevent overloading of the MDU Main CB.
- Nema 1 Enclosure w/removable panels)
- Door-in-door construction; door locks
- Top or bottom entry
- GE 250-600A Subfeed CBs w/opt electr trip
- Subfeed Monitoring Available
- Intelligent Monitor with true RMS metering
- Modbus RTU Communications
- Transient Network, Surge Suppression, Lightning Arrestor options
Related Products
Model MDU-CL (Classic Design)Product Description
Electrical Specs | |
---|---|
KVA: | 400, 500, 625, 750, 1000 |
Input: | 480VAC 3ph 3w + gnd |
Output | 208/120VAC 3ph 4w + gnd |
Frequency | 60Hz |
Efficiency | 98% |
Transformer Specs |
---|
K13 Rated; DOE2016 Compliant |
Class R Insulation, 150° C rise |
Common & Traverse Noise Protection |
200% Output Neutral |
60Hz or 50Hz |
Branch Circuit Monitoring |
---|
Solid Core CT's on each pole |
Data Acquisition Board |
BCMS Basic - Branch Ckt Current Readings |
BCMS + - Panelboard Current, Voltage, KVA, KW, PF, Freq, kVAR, & THDv Readings |
Local readings on the Intelligent Monitor |
Remote Readings via Modbus RTU or optional SNMP |